Understanding Battery Cell Balancing: Passive Balancing, Top and Bottom Balancing, Odd-Even Control, and SOC Compensation

passive balancing for pouch battery cell

A Technical Guide to Battery Balancing Principles, Circuit Design, Execution Strategies, and Capacity Compensation in Battery Management Systems

When discussing battery cell balancing, three fundamental engineering questions need to be answered.

Question 1 — When Should Cells Be Aligned?

Should individual cells reach their upper charging limits together through top balancing, or should they reach their lower discharge limits together through bottom balancing?

Question 2 — Can Adjacent Balancing Channels Operate Simultaneously?

Can neighboring cell balancing switches be activated at the same time, or does the hardware require alternating odd-even channel control?

Question 3 — How Much Charge Has Actually Been Removed?

How can balancing voltage, balancing resistance, duty cycle, and operating time be used to calculate balancing current and capacity?

This article establishes an overall framework for battery balancing before focusing on one of the most widely adopted engineering approaches: online passive balancing.

1. Why Is Battery Cell Balancing Necessary?

What Is Battery Cell Balancing?

Battery cell balancing is the process of reducing differences in the state of charge or voltage among individual cells or parallel cell groups connected in series.

Its objective is to improve the utilization of the entire battery pack while keeping individual cells within their safe operating limits.

What Is the Purpose of Battery Balancing?

The primary purpose is to reduce the impact of the weakest-cell effect, also known as the barrel effect.

In a series-connected battery pack, usable capacity is constrained by the cells that first reach their charging or discharging limits.

During charging, when one cell reaches its upper voltage limit, the Battery Management System (BMS) may need to reduce or terminate charging, even though other cells are not fully charged.

During discharging, when one cell reaches its lower voltage limit, the BMS must protect that cell by limiting or terminating discharge.

As a result:

  • Some cells cannot be fully charged.
  • Some cells retain unused energy after discharge.
  • Available battery pack capacity decreases.
  • Cell voltage differences may increase over repeated cycles.
  • Cells repeatedly operating near their limits may experience additional degradation.

Battery balancing helps reduce avoidable losses caused by differences in cell SOC.

However, balancing cannot restore capacity that has already been lost through irreversible cell aging. Cells with significantly different actual capacities cannot necessarily reach both their upper and lower limits simultaneously.

Battery balancing is not about creating additional capacity. It is about making better use of the capacity already available within the battery pack.

Article content

Figure 1. The weakest-cell effect: usable battery pack capacity is constrained by individual cell operating limits.

2. Active Balancing vs. Passive Balancing

Battery balancing technologies can generally be divided into two categories: passive balancing and active balancing.

Passive Balancing: Dissipating Excess Energy

Passive balancing removes excess charge from selected cells through resistors.

A balancing resistor and an electronic switch, typically a MOSFET, form a discharge path across an individual cell or cell group.

When the switch is activated, electrical energy is converted into heat through the resistor.

The charge of the selected cell gradually decreases, helping reduce SOC differences within the battery pack.

Active Balancing: Transferring Excess Energy

Active balancing redistributes energy instead of simply dissipating it.

Depending on the circuit topology, inductors, capacitors, transformers, or power converters transfer energy:

  • From higher-SOC cells to lower-SOC cells
  • From individual cells to the battery pack
  • From the battery pack to selected cells

This approach can improve energy utilization and support higher balancing currents.

Key Differences Between Active and Passive Balancing

Article content

The current and efficiency figures are illustrative engineering references. Actual performance depends on circuit topology, component selection, and operating conditions.

Why Is Passive Balancing Widely Used in Engineering?

① Cost and Reliability

Passive balancing generally requires fewer components.

A resistor, switching device, and associated control circuit can provide a relatively straightforward balancing solution.

Active balancing requires additional energy-transfer components and control circuits, increasing hardware complexity and development costs.

② Balancing Requirements Are Often Limited

In a well-designed battery pack assembled from carefully matched cells, differences in SOC may remain relatively small during normal operation.

Under these conditions, low-current balancing can be sufficient, provided adequate balancing time is available.

③ Higher Balancing Current Is Not Always Necessary

One illustrative engineering guideline is a balancing-current-to-capacity ratio of approximately 1:1000.

For example, a 100 Ah cell might be paired with a 100 mA balancing circuit.

However, this is not a universal design standard. The required balancing current depends on the expected imbalance, available balancing time, and operating strategy.

④ Thermal Management Is Relatively Straightforward

Passive balancing generates heat, but its dissipation locations and approximate power levels can be calculated.

With appropriate resistor selection, temperature monitoring, PCB layout, and channel scheduling, the thermal load can be managed.

For many battery applications, passive balancing therefore offers a practical combination of cost, simplicity, and reliability.

3. Two Operating Modes of Passive Balancing: Online and Offline Balancing

Passive balancing can be further classified according to the operating state of the BMS.

Online Balancing

Online balancing operates while the Battery Management Unit (BMU) is awake and functioning normally.

The BMU evaluates cell conditions, calculates balancing requirements, and controls balancing execution.

The process may consider cell voltage, SOC, SOH, temperature, charging status, and other operating conditions.

Offline or Sleep-Mode Balancing

In architectures supporting autonomous balancing, offline balancing can continue while the main BMU is in sleep mode.

The Cell Monitoring Unit (CMU) or associated monitoring hardware independently executes balancing according to predefined instructions and safety conditions.

This can extend the available balancing window without requiring the entire BMS to remain fully active.

Not every BMS architecture supports this function.

The remainder of this article focuses specifically on online passive balancing.

4. The Circuit Principle of Passive Balancing

Article content

Figure 2. Passive balancing circuit: a balancing resistor and switching device connected across each series cell group.

Circuit Structure

A battery pack consists of multiple cells or parallel cell groups connected in series.

In a conventional passive balancing circuit, each monitored series group has a parallel discharge path containing:

  • A balancing resistor, R_bal
  • A balancing switch, typically a MOSFET
  • Associated monitoring and control circuitry

When the MOSFET is switched on, current flows through the balancing path, gradually removing charge from the selected cell.

The Four-Step Balancing Control Process

Step 1 — Calculation

The BMU evaluates which cells require balancing and estimates the amount of charge that should be removed.

Step 2 — Request

The BMU sends balancing commands to the corresponding CMU.

Step 3 — Switching

The CMU activates the selected balancing switches, subject to hardware and safety restrictions.

Step 4 — Dissipation

The selected cells discharge through their balancing resistors, converting electrical energy into heat.

The BMU continues monitoring cell conditions and adjusts or terminates balancing when the target or a safety limit is reached.

The underlying principle is straightforward:

The switch closes, the resistor generates heat, and the remaining charge of the selected cell decreases.

5. How Is the Required Balancing Capacity Calculated?

Before balancing can be executed, the BMS must estimate how much charge needs to be removed from each selected cell.

Step 1: Estimate the Remaining Charge of Each Cell

A simplified estimation method is:

Q_remaining = Q_rated × SOC × SOH

Where:

  • Q_remaining = Estimated remaining charge
  • Q_rated = Rated cell capacity
  • SOC = State of Charge
  • SOH = Capacity-based State of Health

SOC and SOH are expressed as decimal fractions in this calculation.

This model assumes that SOC is referenced to the cell’s estimated present full-charge capacity and that SOH represents capacity retention.

Step 2: Calculate the Required Balancing Capacity

For a simplified remaining-charge alignment strategy:

Q_required,i = Q_remaining,i − Q_remaining,min

Where:

  • Q_required,i = Required balancing capacity of cell i
  • Q_remaining,i = Estimated remaining charge of cell i
  • Q_remaining,min = Minimum remaining charge among the cells

When the calculated difference exceeds a predefined balancing threshold, the cell may be identified as requiring balancing.

Example: Three 100 Ah Cells Connected in Series

Assume that all three cells originally have a rated capacity of 100 Ah.

Article content

Cell 3 has the lowest estimated remaining charge at 25 Ah.

Under this simplified remaining-charge alignment calculation:

  • Cell 1 has a charge difference of 45 Ah.
  • Cell 2 has a charge difference of 25 Ah.
  • Cell 3 has no excess charge relative to the selected reference.
Article content

Figure 3. Example of remaining-charge estimation and balancing capacity calculation for three series-connected cells.

This example demonstrates an important principle:

Cell voltage alone does not provide a complete picture of available battery capacity.

A significantly aged cell may have a voltage similar to that of a healthy cell while storing substantially less charge.

Voltage-based balancing is useful, but more advanced BMS strategies may also incorporate SOC and SOH estimation.

However, the example represents a deliberately severe capacity mismatch rather than a normal balancing condition.

At a passive balancing current of 100 mA, removing 45 Ah would theoretically require 450 hours of continuous balancing.

Such a large imbalance would normally justify battery diagnostics and possible cell or pack replacement rather than routine passive balancing.

Furthermore, the appropriate calculation depends on whether the BMS is targeting top balancing, bottom balancing, or another SOC alignment objective.

6. Two Balancing Objectives: Top Balancing and Bottom Balancing

The same balancing hardware can support different control objectives.

The two fundamental approaches are top balancing and bottom balancing.

Top Balancing: Alignment at the End of Charging

Top balancing aims to bring individual cells toward their respective upper SOC or voltage limits at approximately the same time.

Its primary objectives are to:

  • Reduce premature charging termination
  • Improve charging capacity utilization
  • Prevent individual cells from reaching excessive voltage
  • Reduce cell voltage differences near full charge

Top balancing is widely used in lithium battery systems, particularly where batteries are regularly charged close to their upper operating limits.

Bottom Balancing: Alignment at the End of Discharging

Bottom balancing aims to bring individual cells toward their respective lower SOC or voltage limits at approximately the same time.

Its primary objectives are to:

  • Reduce premature discharge termination
  • Improve discharge capacity utilization
  • Prevent individual cells from reaching excessively low voltage
  • Reduce remaining-charge differences near the end of discharge

Top Balancing vs. Bottom Balancing

Article content
Article content

Figure 4. Comparison of top balancing and bottom balancing objectives.

When cells have different actual capacities, aligning them at one end does not necessarily align them at the other.

Therefore, selecting the balancing objective requires consideration of battery chemistry, operating SOC range, charging behavior, aging characteristics, and application requirements.

The two objectives may use similar hardware but require different control strategies.

7. Odd-Even Balancing: Why Can’t Adjacent Channels Always Be Activated Together?

One frequently overlooked aspect of passive balancing circuit design is whether adjacent balancing channels can operate simultaneously.

This capability depends on the architecture of the Analog Front End (AFE), balancing IC, and external switching circuit.

Some designs support simultaneous balancing of neighboring cells.

Others require adjacent channels to operate at different times.

Why Can Simultaneous Activation Cause Problems?

In certain balancing circuit topologies, neighboring channels share resistive or switching paths.

When adjacent channels are activated simultaneously, a shared resistor may be bypassed, changing the effective current path.

Consider a simplified example of such a topology.

When one channel operates independently:

I_single = U / (2R + Rds)

When two adjacent channels operate simultaneously:

I_adjacent ≈ 2U / (2R + Rds)

Where:

  • U = Cell voltage
  • R = Resistance of an individual resistor in the balancing path
  • Rds = MOSFET on-state resistance

Under these specific circuit assumptions, the effective current can approach twice the original value.

This may lead to:

  • Excessive balancing current
  • Resistor overheating
  • Increased MOSFET thermal stress
  • Abnormal external switching behavior
  • Cell voltage measurement disturbances

These equations illustrate a particular shared-resistance topology and should not be generalized to every balancing circuit.

Whether adjacent channels can be activated together must be determined from the AFE datasheet and the actual circuit design.

Article content

Figure 5. In certain shared-resistance circuits, simultaneous activation of adjacent balancing channels changes the effective current path.

The Solution: Odd-Even Grouping and Alternating Activation

When adjacent channels cannot operate simultaneously, a practical solution is to divide the balancing channels into two nonadjacent groups:

Odd-numbered channels: 1, 3, 5, 7, 9…

Even-numbered channels: 2, 4, 6, 8, 10…

The BMS alternates between these groups.

For example, assume cells 1, 2, 4, and 5 require balancing.

Article content

The process repeats until the required balancing capacity has been reached or another termination condition is triggered.

The duration of each activation period can be calibrated according to hardware capabilities, thermal conditions, measurement requirements, and balancing objectives.

Article content

Figure 6. Odd-even balancing execution through alternating activation of nonadjacent channels.

Odd-even scheduling can prevent prohibited adjacent-channel combinations, but it also reduces the effective balancing duty cycle.

This must be considered when calculating actual balancing capacity.

8. Balancing Capacity Compensation: How Much Charge Has Actually Been Removed?

During passive balancing, charge is continuously removed from selected cells.

If the BMS does not account for this additional discharge, its individual cell SOC estimates may gradually drift.

This is why balancing capacity compensation is important.

Calculating Balancing Current

The approximate instantaneous balancing current when the switch is on is:

I_on = U / R_eff

Considering the balancing duty cycle:

I_bal = (U / R_eff) × D

Where:

  • I_bal = Average balancing current
  • U = Balancing voltage
  • R_eff = Effective resistance of the balancing path
  • D = Balancing duty cycle, expressed as a decimal between 0 and 1

The effective resistance may include the balancing resistor, MOSFET on-state resistance, and other relevant circuit resistance.

Calculating Balancing Capacity

When voltage, resistance, and duty cycle remain approximately constant:

Q_bal = I_bal × t

Where:

  • Q_bal = Removed charge in Ah
  • I_bal = Average balancing current in A
  • t = Total elapsed balancing period in hours

If actual switch-on time is used instead of total elapsed time, the duty cycle should not be applied a second time.

For changing operating conditions, balancing capacity can be calculated through integration:

Q_bal = ∫ I_bal(t) dt

Practical Calculation Example

Assume the following balancing parameters:

Article content

The instantaneous balancing current is:

I_on = 4.0 / 40 = 0.1 A

The average balancing current is:

I_bal = 0.1 × 50% = 0.05 A

The total removed charge is:

Q_bal = 0.05 × 4 = 0.2 Ah

The corresponding SOC reduction is:

ΔSOC = 0.2 / 100 × 100% = 0.2 percentage points

The BMS should account for this additional charge removal in its cell-level SOC estimation.

Why Is SOC Compensation Necessary?

In a series-connected battery pack, the main current sensor measures the pack current.

However, passive balancing creates additional local discharge paths across individual cells.

These local currents may not be captured by the main pack current sensor.

Without appropriate compensation, the estimated SOC of balanced cells may become higher than their actual SOC.

Over repeated balancing cycles, this error can accumulate.

An effective BMS should therefore coordinate:

  • Pack current measurement
  • Individual cell voltage monitoring
  • SOC and SOH estimation
  • Balancing current calculation
  • Balancing duty-cycle tracking
  • Balancing capacity compensation

Balancing execution and SOC estimation should operate as an integrated control process rather than two independent functions.

9. Conclusion: Battery Balancing Is More Than a Resistor and a Switch

This article has focused on online passive balancing, covering its fundamental principles, circuit architecture, execution strategy, and SOC compensation.

However, almost every aspect of battery balancing deserves deeper technical investigation.

Active Balancing vs. Passive Balancing

How should engineers choose between energy redistribution and energy dissipation?

Online Balancing vs. Offline Balancing

How can balancing be coordinated between active BMS operation and sleep-mode operation?

Top Balancing vs. Bottom Balancing

Which alignment strategy provides the greatest value for a particular battery chemistry and application?

Odd-Even Balancing

How can balancing channels be scheduled efficiently while respecting AFE hardware restrictions and thermal limits?

Balancing Current and Capacity Compensation

How can the BMS accurately calculate removed charge and maintain reliable SOC estimates?

These questions are particularly relevant to industrial UAV batteries, where high discharge currents, strict weight limitations, frequent charging cycles, and demanding operating environments place additional requirements on battery management systems.

For high-series UAV battery packs, effective balancing can help reduce avoidable cell voltage differences, improve usable energy, and support more consistent battery performance.

However, balancing is not a substitute for high-quality cells, appropriate cell matching, reliable manufacturing, or effective battery protection.

Ultimately, a well-designed battery balancing system must achieve a practical balance between:

Balancing speed, energy efficiency, thermal management, hardware cost, SOC accuracy, and operational reliability.

The goal is not simply to make every cell display the same voltage.

The real goal is to maximize usable battery pack energy while keeping every cell within its safe operating limits throughout the battery’s service life.


UniquePower | UAV Battery & Charging Solutions

We support industrial UAV manufacturers and system integrators with lithium-ion cell selection, customized battery packs, intelligent BMS integration, and charging solutions tailored to specific aircraft and mission requirements.